Track System Specifications:

CUBI-TRAC® Model 110-C CEILING MOUNTED:  Cubicle tracks shall be of 16 gauge extruded, anodized aluminum, entirely, enclosed, except for slot in bottom. Cubicle carriers shall be composed of a non- binding, abrasion-resistant, nylon block supported from self-lubricating bearings by two nylon wheels and contain a free-moving plated swivel-hook assembly. Carriers shall be spaced on 6 inch centers. One end of each track shall be fitted with a removable end stop to permit simple carrier replacement. Splicing clamps shall be of anodized aluminum. Curves shall be factory curved to a 12 inch radius. Model 110-C as manufactured by ADC Hospital Equipment Division of Automatic Devices Company, Allentown, PA, USA.

Shipping weight: approximately 1 lb. per ft

CUBI-TRAC® Model 110-S SUSPENDED:  Cubicle tracks shall be of 16 gauge extruded, anodized aluminum, entirely ,enclosed, except for slot in bottom. Cubicle carriers shall be composed of a non- binding, abrasion-resistant, nylon block supported from self-lubricating bearings by two nylon wheels and contain a free-moving plated swivel-hook assembly. Carriers shall be spaced on 6 inch centers. Curves shall be factory curved to a 12 inch radius. One end of each track shall be fitted with a combination wall flange-end stop to permit simple carrier replacement. Ceiling hanger assemblies shall be spaced approximately six feet apart and consist of joining sleeves, anodized aluminum suspension tubes, ceiling flanges, track sockets and wall flanges. Model 110-S as manufactured by ADC Hospital Equipment Division of Automatic Devices Company, Allentown, PA, USA.

Shipping weight: approximately 1 1/2 lb. per ft.

Switch Specifications:

TWO-WAY SWITCH Model 1165 is a simple device that can provide substantial savings in cubicle curtain costs, since fewer curtains must be purchased, laundered, and eventually replaced. The device also simplifies room layout and furniture placement, because the curtain can be stacked at any of the three walls that the track assembly abuts. The switch consists of a slide-bar mechanism that is easily operated by pulling the curtain in the desired direction. The switch includes a positive stop and guard which prevents the carriers from dropping out of the un-switched track section.